Chapter 24
Three-Phase Voltage
Generation
|
|
|
|
Three-phase generators |
|
Three sets of windings and produce
three ac voltages |
|
Windings are placed 120° apart |
|
Voltages are three identical sinusoidal
voltages 120° apart |
Three-Phase Voltage
Generation
|
|
|
|
Set of voltages such as these are
balanced |
|
If you know one of the voltages |
|
The other two are easily determined |
Four-Wire Systems
|
|
|
|
Three loads have common return wire
called neutral |
|
If load is balanced |
|
Current in the neutral is zero |
|
Current is small |
|
Wire can be smaller or removed |
|
Current may not be zero, but it is very
small |
Four-Wire Systems
|
|
|
Outgoing lines are called line or phase
conductors |
Three-Phase Relationships
|
|
|
|
Line voltages |
|
Voltages between lines either at the
generator (EAB) or at the load (VAB) |
Three-Phase Relationships
|
|
|
|
|
Phase voltages |
|
Voltages across phases |
|
For a Y load, phases are from line to
neutral |
|
For D load, the phases are from line to line |
Three-Phase Relationships
|
|
|
|
Line currents |
|
Currents in line conductors |
|
Phase currents |
|
Currents through phases |
|
For a Y load two currents are the same |
Voltages in a Wye Circuit
|
|
|
|
For a balanced Y system |
|
Magnitude of line-to-line voltage
is times the magnitude of phase
voltage |
|
Each line-to-line voltage |
|
Leads corresponding phase voltage by 30° |
|
Line-to-line voltages form a balanced
set |
Voltages for a Wye
Circuit
|
|
|
|
Nominal voltages |
|
120/208-V |
|
277/480-V |
|
347/600-V systems |
Voltages for a Wye
Circuit
|
|
|
|
Given any voltage at a point in a
balanced, three-phase Y system |
|
Determine remaining five voltages using
the formulas |
Currents for a Wye
Circuit
|
|
|
|
|
Line currents |
|
Same as phase currents |
|
Ia = Van/Zan |
|
Line currents form a balanced set |
|
If you know one current |
|
Determine the other five currents by
inspection |
Currents for a Delta Load
|
|
|
|
In a balanced delta |
|
The magnitude of the line current
is times the magnitude of the phase
current |
Currents for a Delta Load
|
|
|
|
Each line current lags its
corresponding phase current by 30° |
|
For any current in a balanced,
three-phase delta load |
|
Determine remaining currents by
inspection |
|
|
Power in a Balanced
System
|
|
|
|
To find total power in a balanced
system |
|
Determine power in one phase |
|
Multiply by three |
|
Use ac power formulas previously
developed |
Power in a Balanced
System
|
|
|
Since magnitudes are the same for all
three phases, simplified notation may be used |
Active Power to a
Balanced Wye Load
|
|
|
Pf = VfIf cos qf |
|
PT
= 3Pf = 3VfIf cos qf |
|
PT
= VLIL cos
qf |
|
Pf = If2Rf |
|
PT
= 3If2Rf |
Reactive Power to a
Balanced Wye Load
|
|
|
Qf = VfIf sin qf |
|
QT
= VLIL sin
qf |
|
Qf = If2Xf |
|
Units are VARs |
Apparent Power to a
Balanced Wye Load
|
|
|
Sf = VfIf |
|
ST
= VLIL |
|
Sf = If2Zf |
|
|
Apparent Power to a
Balanced Wye Load
|
|
|
Units are VAs |
|
Power factor is |
|
Fp = cos qf = PT/ST = Pf/Sf |
|
|
Power to a Balanced Delta
Load
|
|
|
|
Power formulas for D load are identical to
those for Y load |
|
In all these formulas |
|
Angle qf is phase angle of the load impedance |
Power to a Balanced Delta
Load
|
|
|
|
You can also use single-phase
equivalent in power calculations |
|
Power will be power for just one phase |
Measuring Power in
Three-Phase Circuits
|
|
|
Measuring power to a 4-wire Y load
requires three wattmeters (one meter per phase) |
|
Loads may be balanced or unbalanced |
|
Total power is sum of individual powers |
Measuring Power in
Three-Phase Circuits
|
|
|
|
If load could be guaranteed to be
balanced |
|
Only one meter would be required |
|
Its value multiplied by 3 |
Measuring Power in
Three-Phase Circuits
|
|
|
|
For a three-wire system |
|
Only two meters are needed |
|
Loads may be Y or D |
|
Loads may be balanced or unbalanced |
|
Total power is algebraic sum of meter
readings |
Measuring Power in
Three-Phase Circuits
|
|
|
|
Power factor for a balanced load |
|
Obtain from wattmeter readings using a
watts ratio curve |
|
|
|
|
Measuring Power in
Three-Phase Circuits
|
|
|
From this, q can be
determined |
|
Power factor can then be determined
from cos q |
Unbalanced Loads
|
|
|
|
Use Ohm’s law |
|
For unbalanced four-wire Y systems
without line impedance |
|
Three-wire and four-wire systems with
line and neutral impedance |
|
Require use of mesh analysis |
Unbalanced Loads
|
|
|
|
One of the problems with unbalanced
loads |
|
Different voltages are obtained across
each phase of the load and between neutral points |
Unbalanced Loads
|
|
|
|
Unbalanced four-wire D systems without line
impedance are easily handled |
|
Source voltage is applied directly to
load |
|
Three-wire and four-wire systems with
line and neutral impedance |
|
Require use of mesh analysis |
Power System Loads
|
|
|
|
Single-phase power |
|
Residential and business customers |
|
Single-phase and three-phase systems |
|
Industrial customers |
|
Therefore, there is a need to connect
both single-phase and three-phase loads to three-phase systems |
Power System Loads
|
|
|
Utility tries to connect one third of
its single-phase loads to each phase |
|
Three-phase loads are generally
balanced |
Power System Loads
|
|
|
|
Real loads |
|
Seldom expressed in terms of
resistance, capacitance, and inductance |
|
Rather, real loads are described in
terms of power, power factors, etc. |